DIN Panel mount - Flow rate indicator D010
- Type
High intensity reflective numeric and alphanumeric LCD, UV-resistant. - Ambient temperature
-40°C to +80°C (-40°F to +176°F). - Displayed functions
Flow rate, Measuring and time units.
The D010 is a local, panel mount indicator to display the actual flow rate. The measuring and time unit to be displayed are simply selected through an alfa-numerical configuration menu. No adhesive labels have to be put on the outside of the enclosure: a weather proof and user friendly solution! The configuration of K-factors or Span and number of decimals is done through software functions, without any sensitive dip-switches or trimmers.
Display | |
---|---|
Type |
High intensity reflective numeric and alphanumeric LCD, UV-resistant. |
Dimensions | 90 x 40mm (3.5" x 1.6"). |
Digits | 5 1/2 very large 26mm (1") digits. Various symbols and measuring units. |
Refresh rate | User definable: fast, 1sec , 3sec, 15sec, 30sec, off. |
Operating temperature | |
Ambient (Safe areas) | -40°C to +80°C (-40°F to +176°F). |
Power requirements | |
Type PB | Long life Lithium battery - life-time depends upon settings and configuration - up to 5 years. |
Type PD | 24V AC/DC ± 10%. Power consumption max. 1 Watt. |
Type PL | Input loop powered from sensor signal 4 - 20mA (requires type A). |
Type PM | 115 - 230V AC ± 10%. Power consumption max. 1 Watt. |
Type PX | 8 - 30V DC. Power consumption max. 0.3 Watt. |
Type ZB | 20 - 30V DC. Power consumption max. 1 Watt. With type PD / PM: internally powered. |
Sensor excitation | |
---|---|
Type PB/PX |
3V DC for pulse signals and 1.2V DC for coil pick-up. |
Note | This is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine wave) and reed-switches. |
Type PD / PM |
for pulse signals: 1.2 / 3 / 8.2 / 12 / 24V DC For analog signals: 8.2 / 12 / 24V DC 8.2V DC, Iout max. 35mA @ 20°C. 12V DC, Iout max. 50mA @ 20°C. 24V DC, Iout max. 75mA @ 20°C. (this voltage can vary depending on the input supply voltage) |
Terminal connections | |
Type | Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2 . |
Data protection | |
Type | EEPROM backup of all settings. Data retention at least 10 years. |
Password | Configuration settings can be password protected. |
Directives & Standards | |
EMC | Directive 2004/108/EC, FCC 47 CFR part 15. |
Low voltage | Directive 2006/95/EC. |
IP & NEMA | EN 60529 & NEMA 250. |
The D-Series is a DIN-sized display and the better alternative for your existing, not waterproof, front panel mount indicators in extreme weather outdoor applications or e.g. in food industries where working environments are often cleaned with powerful water jets.
The D010 fits in flow measurement applications where a local flow rate indication is required without re-transmission or totalizer functionality.